Every building and every factory has distribution boards, and they are among the least discussed pieces of electrical equipment. When they are designed well, nobody notices. When they are designed badly, the symptoms are familiar: nuisance tripping, hot breakers, a busbar that cannot take one more circuit, or a board that fails the first time a real fault occurs.
A distribution board is far more than a metal box with breakers in it. Its busbar, incomer, protective devices, enclosure and internal layout have to be matched to the real load, the available fault current and the site conditions. In Pakistan, where ambient temperatures regularly pass 45 degrees Celsius and supply conditions vary, getting these matches right matters even more.
This guide explains the three levels of distribution, which parts of IEC 61439-3 and IEC 61439-2 apply, how to size a board step by step, and the design errors that cause problems later. It is written by the panel engineering team at Bilal Switchgear Engineering, which manufactures power distribution boards in Lahore.
The Three Levels of Distribution: MDB, SMDB and DB
Power inside a facility flows through a hierarchy. Each level has a different job and a different design emphasis.
Main Distribution Board (MDB)
The MDB receives power from the transformer or generator and distributes it to the major load groups. It typically has an air circuit breaker or large MCCB incomer, a heavy busbar system, metering, and outgoing MCCBs feeding sub-boards, motor control centres and large loads. Fault levels are highest here, so short-circuit rating and discrimination are the main design concerns.
Sub-Main Distribution Board (SMDB)
An SMDB sits between the MDB and the final boards, usually serving one floor, one production block or one service group. It splits a large feeder into several smaller ones and often includes isolation, metering and surge protection for the zone it serves.
Final Distribution Board (DB)
The final DB feeds the actual circuits: lighting, socket outlets, small motors and equipment. It is the board that ordinary people operate, which is why it falls under IEC 61439-3. Safety features such as RCD protection, shrouded live parts and clear labelling carry the most weight here.
Which IEC 61439 Part Applies
IEC 61439-2 covers power switchgear and controlgear assemblies, which is the standard for MDBs, SMDBs and industrial boards operated by trained staff. IEC 61439-3 covers distribution boards intended to be operated by ordinary persons, with rated current up to 250 A and rated voltage up to 1,000 V AC. A final DB in an office, school or shop sits under Part 3. A large industrial MDB sits under Part 2. Both rely on the general rules in IEC 61439-1.
Whichever part applies, the board should carry design verification evidence and a routine test record, so that the buyer knows the design has been proven and the unit itself has been tested.
How to Size a Distribution Board Step by Step
Step 1: Build the Load Schedule
List every outgoing circuit with its connected load, current and power factor. Group loads by type (lighting, sockets, motors, HVAC) so that diversity can be applied sensibly. Include known future loads, not just today’s.
Step 2: Apply the Rated Diversity Factor
Not every circuit runs at full load at the same time, and IEC 61439-1 recognises this through the rated diversity factor (RDF). The standard values are 0.9 for 2 or 3 circuits, 0.8 for 4 or 5, 0.7 for 6 to 9 and 0.6 for 10 or more. Note that the RDF is a design assumption declared by the manufacturer, and the board must be built and verified for that assumption. The load schedule must not exceed it.
Worked example: a board has 8 outgoing circuits of 63 A each. Total connected current is 8 x 63 = 504 A. With an RDF of 0.7 for 6 to 9 circuits, the busbar must carry 504 x 0.7 = 353 A. A 400 A busbar system is therefore suitable if the real load really does stay within that diversity. If all 8 circuits are motor loads that run together, the true diversity is closer to 1.0 and the busbar must be sized for 504 A, so a 630 A system is needed.
Step 3: Select the Incomer Rating
The incomer must carry the diversified load with margin, coordinate with the upstream protection and be rated at or above the board’s declared current. Add the spare capacity allowance before choosing the standard rating, not after.
Step 4: Check Busbar Rating and Short-Circuit Withstand
The busbar current rating must cover the diversified load, and its short-circuit withstand (Icw) or conditional short-circuit rating must be at or above the prospective fault current at the board. A 1,000 kVA transformer with 5 percent impedance, for example, gives roughly 1,000 / (1.732 x 0.415 x 0.05) = about 27.8 kA at 415 V, so the board needs a rating above that value, and the next standard step is selected. The figures should appear on the single line diagram so that everyone can see the basis.
Step 5: Allow Spare Capacity
Allow roughly 20 to 25 percent of spare ways, with space and busbar capacity to use them. A board that is full on the day it is energised forces an expensive replacement the first time the facility grows.
Selecting Protective Devices
- MCCBs (IEC 60947-2): used for incomers and larger outgoing feeders, with adjustable thermal and magnetic settings. Breaking capacity must meet the fault level at the device location
- MCBs: used on final circuits in building installations, with the breaking capacity and trip curve (B, C or D) chosen for the load. Type C suits most mixed loads and Type D suits high inrush equipment
- RCDs: 30 mA devices give personal protection on socket and general circuits, while 300 mA devices are used for fire protection at higher levels. Choose the type (AC, A or F) for the load electronics; variable speed drives may need Type B
- Surge protection devices: fitted at the MDB and critical sub-boards as part of a coordinated scheme, as described in our guide to earthing and lightning protection
- Discrimination: upstream and downstream devices must be coordinated so that a final circuit fault trips only the nearest breaker. Manufacturers publish discrimination tables for their own device ranges
Heat and Pakistani Ambient Conditions
IEC 61439-1 assumes an ambient air temperature not exceeding 40 degrees Celsius, with a 24-hour average not above 35 degrees Celsius. Many Pakistani switchrooms, rooftops and factory floors exceed this in summer. Every device inside a board produces heat, and that heat has to leave the enclosure. If the ambient is above the reference, breakers must be derated using the manufacturer’s tables, ventilation or air conditioning must be provided, or a larger enclosure with more heat dissipation area must be used.
Heat problems appear as nuisance tripping on hot afternoons and as discoloured insulation near terminals. Both can be avoided in the design stage by checking the total device losses against the enclosure’s ability to dissipate heat.
Enclosure, Protection Rating and Internal Separation
Degree of Protection
IP31 to IP41 is common for clean indoor switchrooms, IP54 for dusty indoor areas such as textile and cement plants, and IP65 for outdoor or wash-down locations. The rating applies to the complete enclosure with cable entries fitted, so gland plates and sealing matter.
Form of Internal Separation
IEC 61439-2 defines Forms 1 to 4. Form 1 has no separation, while Form 4 separates busbars, functional units and terminals. Industrial boards commonly use Form 2b or 3b to give maintenance staff more protection and to limit the effect of a fault in one compartment.
Materials and Finish
Powder-coated sheet steel is the standard for most boards. Stainless steel or polycarbonate suits corrosive or hygienic environments. Specify the finish, since the paint system affects durability in humid and coastal conditions.
Labelling, Documentation and Testing
- Circuit labels on every outgoing way, matching the circuit schedule and the drawings
- Manufacturer nameplate with rated voltage, current, short-circuit rating, IP rating and standard
- A single line diagram and circuit schedule kept in or beside the board, updated to as-built condition
- Routine test records covering insulation, earth continuity, mechanical operation and function
- Device settings recorded for adjustable breakers and RCDs
Common Distribution Board Design Errors
- Choosing busbar current on connected load alone, ignoring diversity or applying a diversity the board was never verified for
- Fault level not checked, leaving breaking capacity below the prospective fault current
- No spare capacity, forcing replacement as soon as loads grow
- Ignoring ambient temperature, causing nuisance trips and early insulation ageing
- Poor discrimination, so a final circuit fault drops an entire floor
- Missing or wrong labelling, which creates risk during maintenance and fault finding
Distribution Boards from Bilal Switchgear Engineering
Bilal Switchgear Engineering manufactures MDBs, SMDBs and final distribution boards in Lahore through our Power Division. Our engineers prepare the load schedule review, busbar and breaker selection, short-circuit check and drawings as part of each order, and every board is tested before dispatch under our ISO 9001:2015 quality system.
Contact our engineering team to discuss your distribution board requirements or to review an existing load schedule before ordering.
Frequently Asked Questions
What is the difference between MDB, SMDB and DB?
An MDB is the main board receiving power from the transformer or generator and feeding major load groups. An SMDB is a sub-main board serving a floor, block or service group. A DB is the final board feeding lighting, sockets and equipment. Fault levels and device ratings fall at each step down, while safety features for ordinary users matter more at the DB level.
What is the rated diversity factor in IEC 61439?
The rated diversity factor (RDF) is the declared proportion of the sum of all outgoing circuit ratings that the board can carry at the same time. IEC 61439-1 gives standard values of 0.9 for 2 or 3 circuits, 0.8 for 4 or 5, 0.7 for 6 to 9 and 0.6 for 10 or more. The board must be verified for the declared RDF, and the real load must not exceed it.
How much spare capacity should a distribution board have?
A common design allowance is 20 to 25 percent of spare ways, with busbar and incomer capacity to support them. The exact figure depends on how quickly the facility expects to grow, but a board with no spare capacity usually needs replacing at the first expansion.
Does IEC 61439-3 apply to industrial boards?
IEC 61439-3 applies to distribution boards operated by ordinary persons with rated current up to 250 A and voltage up to 1,000 V AC, such as final boards in offices, shops and schools. Industrial MDBs and boards operated by trained staff are built to IEC 61439-2. Both rely on the general rules in IEC 61439-1.
Why do breakers trip in summer on a correctly sized board?
Breakers are rated at a reference ambient, and heat inside an enclosed board adds to the surrounding temperature. When the ambient is above the reference, a breaker carries less current before its thermal element operates. The fix is to check device derating tables, improve ventilation or cooling, or use a larger enclosure.