Air conditioning is the largest electricity consumer in most Pakistani commercial buildings, and the chiller plant is where most of that energy is spent. In a hotel, hospital, mall or office tower, the chillers, pumps and cooling towers together can account for well over half of the building’s HVAC consumption. A plant that is oversized, poorly configured or badly controlled wastes energy every hour of every summer.
Chiller plant design is often treated as an equipment selection exercise: pick a chiller of the right tonnage and move on. In practice the efficiency, reliability and running cost of the plant depend just as much on how the chillers, pumps, cooling towers, pipework and controls are arranged around that equipment.
This guide explains how chilled water plants work, how to choose between air-cooled and water-cooled systems, how to size a plant step by step, and which efficiency measures matter. It is written by the engineering team at Bilal Switchgear Engineering, whose MEP project services include HVAC design and installation for Pakistani commercial and industrial projects.
How a Chilled Water Plant Works
A chiller plant moves heat from the building to the outside air through three connected circuits.
- Chilled water circuit: pumps circulate cold water (typically 6 to 7 degrees Celsius leaving) to air handling units and fan coil units, where it absorbs heat from the building air, and return it to the chiller warmer by 5 to 6 degrees
- Refrigerant circuit: inside the chiller, the compressor, condenser, expansion device and evaporator transfer heat from the chilled water to the condenser
- Heat rejection circuit: the condenser heat, which is the cooling delivered plus the compressor power, goes to the atmosphere either through condenser water and a cooling tower (water-cooled) or directly to air through condenser fans (air-cooled)
Air-Cooled vs Water-Cooled Chillers
Air-Cooled Chillers
Air-cooled chillers reject heat directly to the outdoor air, so they need no cooling tower, condenser water pumps or makeup water. They are simpler to install and maintain and suit small and medium plants and sites where water is scarce. Their weakness in Pakistan is the climate: condensing temperature follows outdoor dry-bulb temperature, so at 45 degrees Celsius or higher the capacity falls and the power draw rises. Always check selection at the project’s real design ambient, using the manufacturer’s performance curves, and not only at standard rating conditions.
Water-Cooled Chillers
Water-cooled chillers reject heat to condenser water cooled by a tower, so condensing temperature follows the wet-bulb temperature, which is much lower than dry-bulb in Pakistan’s dry pre-monsoon months. This gives much better efficiency, typically about 0.5 to 0.65 kW/TR for a good centrifugal machine against about 1.0 to 1.3 kW/TR for air-cooled. The trade-offs are higher first cost, plant room and tower space, water treatment and more maintenance. Water-cooled plants are usually justified above roughly 200 to 300 TR, especially where operating hours are long.
Compressor Types Used in Pakistan
Scroll Chillers
Compact and efficient at small capacities, scroll chillers are common for plants up to a few hundred tons, often in multiple modules.
Screw Chillers
Screw compressors cover medium to large capacities, handle part load well and tolerate hot conditions, which makes them a frequent choice for Pakistani commercial and industrial plants, both air-cooled and water-cooled.
Centrifugal Chillers
Centrifugal machines give the best efficiency at large capacities, particularly with variable speed drives. They suit big hotels, hospitals, malls and campus plants running long hours.
Absorption Chillers
Absorption machines use heat (steam, hot water or gas) instead of electricity as the main energy input. They make sense where cheap waste heat or a gas supply is available, and are otherwise less efficient than electric chillers.
How to Size a Chiller Plant Step by Step
Step 1: Calculate the Cooling Load
Use a proper heat load calculation covering solar gain, envelope conduction, people, lighting, equipment and fresh air. Rules of thumb based on floor area are useful only for early budgeting, because fresh air and equipment loads vary enormously between building types.
Step 2: Apply Diversity and Avoid Oversizing
Not every zone peaks at the same time, so the plant capacity is normally lower than the sum of the individual zone loads. Oversizing is a common and costly error: a chiller that is too large runs at low load for most hours, where efficiency is poorer and cycling wears equipment.
Step 3: Split the Plant into Several Chillers
Rather than one large machine, most plants use two to four chillers. Several smaller units match the load more closely, allow maintenance without shutting the building down and provide N+1 redundancy where the building cannot tolerate a cooling failure.
Step 4: Calculate Chilled Water Flow
Worked example: a plant delivers 1,000 kW of cooling (about 284 TR) with a 5.5 degree Celsius chilled water temperature difference. Flow = 1,000 / (4.186 x 5.5) = 43.4 L/s, which is about 156 cubic metres per hour. Condenser heat rejection is roughly 1.15 to 1.25 times the cooling, so about 1,170 kW. At the same temperature difference, the condenser water flow is about 1,170 / (4.186 x 5.5) = 50.8 L/s. These flows size the pumps, pipework and cooling tower.
Efficiency: kW/TR, IPLV and Whole-Plant Performance
Chiller efficiency is quoted in kW per ton (lower is better) or as a coefficient of performance (higher is better). Full-load figures flatter a chiller, because buildings run at full load for only a few hours a year. AHRI 550/590 therefore defines the Integrated Part Load Value (IPLV), which weights efficiency at 100, 75, 50 and 25 percent load by 1, 42, 45 and 12 percent. Most operating hours sit around 50 to 75 percent load, so IPLV is the number that predicts real energy use better than full-load efficiency.
Chiller efficiency is also only part of the story. The chilled water pumps, condenser water pumps and cooling tower fans all consume energy, so the plant efficiency in kW/TR including every auxiliary is the honest measure. Energy standards such as ASHRAE 90.1 set minimum chiller efficiencies and encourage variable flow and variable speed control.
Illustrative cost example: a 500 TR plant running the equivalent of 4,000 full-load hours per year at plant efficiencies of 0.85 and 0.65 kW/TR. The difference is 0.2 kW/TR x 500 TR = 100 kW. Over 4,000 hours that is 400,000 kWh, which at PKR 50 per kWh is PKR 20,000,000 per year. Actual savings depend on the load profile, tariff and equipment, so treat this as a scale indicator, not a quotation.
Plant Configuration and Controls
- Variable primary flow: modulating the chilled water flow with the load saves pump energy, provided each chiller keeps its minimum flow requirement
- Variable speed drives: fitting variable frequency drives on pumps and cooling tower fans reduces energy at part load, using the same cube-law savings described in our VFD guide
- Chiller sequencing: the control system should run the minimum number of chillers at their best efficiency range and stage them in and out automatically
- Condenser water reset: allowing condenser water temperature to fall when the wet-bulb is low improves chiller efficiency, within the manufacturer’s limits
- Integration with the building management system: trending kW/TR, flows and temperatures lets operators find problems early, which is the main benefit of a proper BMS
Designing for Pakistani Conditions
Pakistan places specific demands on a chiller plant. Summer ambient temperatures of 45 degrees Celsius and above reduce air-cooled chiller output, and during the monsoon, high humidity raises the wet-bulb temperature, which reduces cooling tower performance. Selections should be checked at both extremes.
- Water quality: hard water scales condensers and tower fill, so water treatment and a bleed-off system are essential on water-cooled plants
- Dust: filters, tower basins and condenser coils clog quickly in dusty areas, so cleaning access and schedules must be designed in
- Power quality: voltage variation and interruptions affect compressors, so protection, restart logic and sometimes ride-through capability should be considered
- Generator backup: for critical plants, chiller starting current and sequencing must be coordinated with the standby generator and ATS
Commissioning and Maintenance
- Commission against design: verify flows, temperature differences, pump heads and chiller capacity under real load, and record the results as the baseline
- Water treatment: test water regularly and control scale, corrosion and biological growth
- Condenser and tube cleaning: clean on a regular schedule, since fouling raises power consumption noticeably
- Refrigerant and oil checks: monitor levels, leaks and oil condition as part of a planned programme
- Performance trending: log kW/TR so that a drift in efficiency is caught early
Common Chiller Plant Design Errors
- Oversizing the plant based on safety margins stacked on top of each other
- Judging efficiency by full-load figures instead of IPLV and whole-plant kW/TR
- Selecting air-cooled chillers using standard rating conditions instead of the real design ambient
- A single large chiller with no redundancy for a critical building
- No water treatment on a water-cooled plant
- No metering, so energy waste stays invisible
Chiller Plant Design by Bilal Switchgear Engineering
Our MEP Division designs and installs chilled water systems, including load calculations, chiller and pump selection, pipework, controls and electrical supply, as part of coordinated HVAC and electrical packages. Our building management system capability lets the plant controls and energy monitoring be designed together with the mechanical system.
Contact our MEP engineering team to discuss a new chiller plant, a plant upgrade or an efficiency review.
Frequently Asked Questions
What is a ton of refrigeration (TR)?
One ton of refrigeration is 3.517 kW, or 12,000 BTU per hour. It is the standard unit for chiller capacity. A 300 TR chiller therefore delivers about 1,055 kW of cooling.
Should I choose an air-cooled or water-cooled chiller in Pakistan?
Air-cooled chillers are simpler and need no tower or makeup water, so they suit smaller plants and water-scarce sites, but they lose capacity and efficiency in very high ambient temperatures. Water-cooled chillers are more efficient and are usually justified above roughly 200 to 300 TR with long operating hours, but they need a cooling tower, water treatment and more maintenance.
How do I calculate chilled water flow?
Flow in litres per second equals the cooling load in kW divided by 4.186 times the temperature difference in degrees Celsius. For 1,000 kW at a 5.5 degree difference, the flow is about 43.4 L/s, or roughly 156 cubic metres per hour.
What is IPLV and why does it matter?
IPLV is the Integrated Part Load Value defined in AHRI 550/590. It weights chiller efficiency at 100, 75, 50 and 25 percent load by 1, 42, 45 and 12 percent. Because buildings spend most hours at part load, IPLV predicts real energy use better than full-load efficiency.
How many chillers should a plant have?
Most plants use two to four chillers instead of one large unit. Several machines follow the load more closely, allow maintenance without a full shutdown and can provide N+1 redundancy for hospitals, data centres and hotels where cooling cannot be lost.